Thermal considerations in cooling large scale high compute density data centers

C. D. Patel, R. Sharma, C. E. Bash, Abdlmonem Beitelmal

Research output: Chapter in Book/Report/Conference proceedingConference contribution

78 Citations (Scopus)

Abstract

A high compute density data center of today is characterized as one consisting of thousands of racks each with multiple computing units. The computing units include multiple microprocessors, each dissipating approximately 250 W of power. The heat dissipation from a rack containing such computing units exceeds 10 KW. Today's data center, with 1000 racks, over 30,000 square feet, requires 10 MW of power for the computing infrastructure. A 100,000 square foot data center of tomorrow will require 50 MW of power for the computing infrastructure. Energy required to dissipate this heat will be an additional 20 MW. A hundred thousand square foot planetary scale data center, with five thousand 10 KW racks, would cost ∼$44 million per year (@ $100/MWh) just to power the servers & $18 million per year to power the cooling infrastructure for the data center. Cooling design considerations by virtue of proper layout of racks can yield substantial savings in energy. This paper shows an overview of a data center cooling design and presents the results of a case study where layout change was made by virtue of numerical modeling to avail efficient use of air conditioning resources.

Original languageEnglish
Title of host publicationInterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM
PublisherIEEE Computer Society
Pages767-776
Number of pages10
Volume2002-January
ISBN (Print)0780371526
DOIs
Publication statusPublished - 2002
Externally publishedYes
Event8th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM 2002 - San Diego, United States
Duration: 30 May 20021 Jun 2002

Other

Other8th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM 2002
CountryUnited States
CitySan Diego
Period30/5/021/6/02

Fingerprint

Cooling
Heat losses
Air conditioning
Microprocessor chips
Servers
Hot Temperature
Costs

Keywords

  • Air conditioning
  • Computational fluid dynamics
  • Cooling
  • Data mining
  • Foot
  • Large-scale systems
  • Numerical models
  • Power system modeling
  • Temperature distribution
  • Thermal management

ASJC Scopus subject areas

  • Control and Systems Engineering
  • Electrical and Electronic Engineering

Cite this

Patel, C. D., Sharma, R., Bash, C. E., & Beitelmal, A. (2002). Thermal considerations in cooling large scale high compute density data centers. In InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM (Vol. 2002-January, pp. 767-776). [1012532] IEEE Computer Society. https://doi.org/10.1109/ITHERM.2002.1012532

Thermal considerations in cooling large scale high compute density data centers. / Patel, C. D.; Sharma, R.; Bash, C. E.; Beitelmal, Abdlmonem.

InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM. Vol. 2002-January IEEE Computer Society, 2002. p. 767-776 1012532.

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Patel, CD, Sharma, R, Bash, CE & Beitelmal, A 2002, Thermal considerations in cooling large scale high compute density data centers. in InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM. vol. 2002-January, 1012532, IEEE Computer Society, pp. 767-776, 8th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM 2002, San Diego, United States, 30/5/02. https://doi.org/10.1109/ITHERM.2002.1012532
Patel CD, Sharma R, Bash CE, Beitelmal A. Thermal considerations in cooling large scale high compute density data centers. In InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM. Vol. 2002-January. IEEE Computer Society. 2002. p. 767-776. 1012532 https://doi.org/10.1109/ITHERM.2002.1012532
Patel, C. D. ; Sharma, R. ; Bash, C. E. ; Beitelmal, Abdlmonem. / Thermal considerations in cooling large scale high compute density data centers. InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM. Vol. 2002-January IEEE Computer Society, 2002. pp. 767-776
@inproceedings{af67749ec1c540158d53f2bded8e9531,
title = "Thermal considerations in cooling large scale high compute density data centers",
abstract = "A high compute density data center of today is characterized as one consisting of thousands of racks each with multiple computing units. The computing units include multiple microprocessors, each dissipating approximately 250 W of power. The heat dissipation from a rack containing such computing units exceeds 10 KW. Today's data center, with 1000 racks, over 30,000 square feet, requires 10 MW of power for the computing infrastructure. A 100,000 square foot data center of tomorrow will require 50 MW of power for the computing infrastructure. Energy required to dissipate this heat will be an additional 20 MW. A hundred thousand square foot planetary scale data center, with five thousand 10 KW racks, would cost ∼$44 million per year (@ $100/MWh) just to power the servers & $18 million per year to power the cooling infrastructure for the data center. Cooling design considerations by virtue of proper layout of racks can yield substantial savings in energy. This paper shows an overview of a data center cooling design and presents the results of a case study where layout change was made by virtue of numerical modeling to avail efficient use of air conditioning resources.",
keywords = "Air conditioning, Computational fluid dynamics, Cooling, Data mining, Foot, Large-scale systems, Numerical models, Power system modeling, Temperature distribution, Thermal management",
author = "Patel, {C. D.} and R. Sharma and Bash, {C. E.} and Abdlmonem Beitelmal",
year = "2002",
doi = "10.1109/ITHERM.2002.1012532",
language = "English",
isbn = "0780371526",
volume = "2002-January",
pages = "767--776",
booktitle = "InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM",
publisher = "IEEE Computer Society",

}

TY - GEN

T1 - Thermal considerations in cooling large scale high compute density data centers

AU - Patel, C. D.

AU - Sharma, R.

AU - Bash, C. E.

AU - Beitelmal, Abdlmonem

PY - 2002

Y1 - 2002

N2 - A high compute density data center of today is characterized as one consisting of thousands of racks each with multiple computing units. The computing units include multiple microprocessors, each dissipating approximately 250 W of power. The heat dissipation from a rack containing such computing units exceeds 10 KW. Today's data center, with 1000 racks, over 30,000 square feet, requires 10 MW of power for the computing infrastructure. A 100,000 square foot data center of tomorrow will require 50 MW of power for the computing infrastructure. Energy required to dissipate this heat will be an additional 20 MW. A hundred thousand square foot planetary scale data center, with five thousand 10 KW racks, would cost ∼$44 million per year (@ $100/MWh) just to power the servers & $18 million per year to power the cooling infrastructure for the data center. Cooling design considerations by virtue of proper layout of racks can yield substantial savings in energy. This paper shows an overview of a data center cooling design and presents the results of a case study where layout change was made by virtue of numerical modeling to avail efficient use of air conditioning resources.

AB - A high compute density data center of today is characterized as one consisting of thousands of racks each with multiple computing units. The computing units include multiple microprocessors, each dissipating approximately 250 W of power. The heat dissipation from a rack containing such computing units exceeds 10 KW. Today's data center, with 1000 racks, over 30,000 square feet, requires 10 MW of power for the computing infrastructure. A 100,000 square foot data center of tomorrow will require 50 MW of power for the computing infrastructure. Energy required to dissipate this heat will be an additional 20 MW. A hundred thousand square foot planetary scale data center, with five thousand 10 KW racks, would cost ∼$44 million per year (@ $100/MWh) just to power the servers & $18 million per year to power the cooling infrastructure for the data center. Cooling design considerations by virtue of proper layout of racks can yield substantial savings in energy. This paper shows an overview of a data center cooling design and presents the results of a case study where layout change was made by virtue of numerical modeling to avail efficient use of air conditioning resources.

KW - Air conditioning

KW - Computational fluid dynamics

KW - Cooling

KW - Data mining

KW - Foot

KW - Large-scale systems

KW - Numerical models

KW - Power system modeling

KW - Temperature distribution

KW - Thermal management

UR - http://www.scopus.com/inward/record.url?scp=84950136782&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=84950136782&partnerID=8YFLogxK

U2 - 10.1109/ITHERM.2002.1012532

DO - 10.1109/ITHERM.2002.1012532

M3 - Conference contribution

AN - SCOPUS:84950136782

SN - 0780371526

VL - 2002-January

SP - 767

EP - 776

BT - InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM

PB - IEEE Computer Society

ER -